10°C to 25°C 33L/Min 17L Capacity Recirculating Chiller


$2,290.00

Compare

WAC-1 digital temperature controlled recirculating water chiller with built-in swivel casters, recommended for our IH series induction heaters (see models below). These chillers have built-in stainless steel tank and water pump for durability and rust-free operation. two sets of water manifolds included for immediate use.

Category:
 Model WAC-1
 Input power 110 VAC 60 Hz single-phase (1PH) 1460 watts
 Nominal cooling capacity 1935 kcal/h
Nominal cooling capacity is according to:
Inlet chilled fluid temperature: 12°C
Outlet chilled fluid temperature: 7°C
Inlet cooling air temperature: 30°C
Outlet cooling air temperature: 35°C
 Compressor Make: Panasonic, UL Listed
Power: 110VAC 60Hz 1-PH, LRA42, thermally protected
Refrigerant: R410A (800g)
Number of compressor installed: one
 Water pump Make: LX (CMFL2-20-A-W-G-BABE)
Power: 110VAC 60Hz 1-PH 370 watts 3.7A 3450 rpm IP55
Flow rate: 528 gallons per hour
Max pressure: 10 bar. H(max); 20.5m, H(n): 16m
 Reservoir volume 4.5 gallons
 Cooling fan Make: Kunli (YWF A2S-300S-5DIIIA05)
Power: 110VAC 60Hz 1-PH 155 watts 1.35A 2700rpm 16uF/500V IP44
Flow rate: 70,000 cu ft per hour
Number of fan installed: one
 Temperature accuracy +/- 2 °C
 Recommended coolant Distilled water
 Water inlet & outlet on chiller KF40 flange
 Manifold Inlet: KF40, outlet: 8mm quick connect with ball valve
 Unit/shipping weight 200 Lb / 260 Lb
 Unit/shipping dimensions 29 x 17 x 35″ / 36 x 21 x 42″ (DxWxH)
Standard package WAC-1 recirculating chiller*1 pc

Water manifold*2 pc

KF40 clamp*2 pc

Users manual*1 pc

 Safety Over current and compressor thermal protection
 Working environment Temperature range of chilled fluid: 5°C – 35°C
Temperature difference of chilled fluid between inlet
and outlet: 3°C – 8°C. It is better to use the chiller while
the ambient  temperature at or below 35°C
Compatiable induction heaters High frequency 4kW, 6.6kW
Mid frequency 15kW, 25kW
Low frequency 15kW
 CE compliant Yes